The NCC contains references to reduced subfloor height and termite management under subfloor ventilation Table 6.2.1b through a reference in the notes (see Table Note 1).
Climatic zone (see Figure 6.2.1a) | Minimum ground clearance height where termite inspection or management system is not required (mm) | Minimum ground clearance height where termite inspection is required (mm) |
A, B and C | 150 | 400 |
Table notes:
The obligation for a termite management system is contained in H1D3 Site Preparation and Subclause (3) refers the reader to Part 3.4 of the Housing Provisions.
(3) Compliance with Part 3.4 of the ABCB Housing Provisions satisfies Performance Requirement H1P1 for termite risk management.
Part 3.4.2 Termite management systems states where a termite management system is required it must comply with AS 3660.1 Termite Management or be tested and passed the test required by section 5 of AS 3660.3.
The Standard AS 3660.1 is a Deemed-to-Satisfy solution for physical and chemical barriers to deter termites, which references the following relevant subfloor height requirements under Clause 2.4 of the standard:
Clearances are detailed in 3.3.2 Access for visual inspection which states the following shall apply:
Therefore, if a height which does does not meet subclause (a) and (b) and access for visual maintenance can’t be achieved, the only option the standard provides is a chemical barrier. Clause 7.7.3 of the standard states that where compliance with 3.3.2 can’t be achieved (400 mm clearance) all areas of the subfloor, soil shall be treated.
A chemical termite management system throughout the subfloor area and horizontal elements would therefore allow the overall height of the subfloor to reach 150 mm, providing other considerations relating to subfloor ventilation can be achieved.