The NCC provisions have for many years required Class 2-9 buildings with an effective height of greater than 25m to be sprinkler protected. NCC 2019 now requires Class 2 (apartments, multi-residential units, etc.) and Class 3 buildings (hotels, motels, etc.) with a rise in storeys of four or more to be sprinkler protected.
This change represents a substantial shift as the NCC moves away from the previous approach of passive protection for buildings with an effective height less than 25m. They will now need to be designed using a combination of active (sprinklers) and passive systems.
NCC Volume One Clause E1.5 provides a requirement for the installation of a sprinkler system through Table E1.5. The provisions are as follows:
A sprinkler system must:
Extract from NCC 2019 Table E1.5 (highlighted text indicates the new NCC 2019 provisions)
Occupancy | Where sprinklers are required |
All classes—
|
Throughout the whole building if any part of the building has an effective height of more than 25m. |
Class 2 or 3 building (excluding a building used as a residential care building) and any other class of building (excluding a building used as a residential care building) containing a Class 2 or 3 part. | Throughout the whole building, including any part of another class, if any part of the building has a rise in storeys of four storeys or more and an effective height of not more than 25m. |
Specification E1.5a sets out the requirements for the design and installation of fire sprinkler systems and concessions for Class 2 and 3 buildings not more than 25m in effective height with a rise in four storeys or more.
The changes include the introduction of two new sprinkler standards: FPAA101D and FPAA101H. These standards provide offsets to the installation of a full AS 2118.1 sprinkler system.
As part of introducing the new requirements, depending on which sprinkler system is being provided, there are a number of concessions or offsets that are permitted to be used in the design and construction of the Class 2 or 3 building.
These are located in the following clauses of Specification E1.5a and are as follows:
Class 2 and 3 buildings fitted with AS 2118.1 or 2118.4 sprinkler systems must be constructed in accordance with Specification E1.5a (2(b) and the permitted concessions under clause 3(a) include:
The concessions for the FPPA101D and FPPA101H sprinkler are similar with the exception that the FPPA101D systems will require internal hydrants to be installed if there is no external hydrant to serve the building or there is no dry hydrant system installed in the building.
Some of the concessions include:
As noted above the changes include the introduction of two new sprinkler standards produced by the Fire Protection Association of Australia (FPAA) now referenced by the NCC: FPAA101D and FPAA101H.
These two standards have been developed based on a domestic-type sprinkler system and are being promoted as a more cost-effective option to the installation of a full AS 2118.1 system, as well as providing some concession to the passive construction requirements of the building.
It is important to note that FPAA101D and FPAA101H provide concessions to the corresponding requirements in AS 2118 and must be read in conjunction with those standards.
The FPPA101D Standard is a new design standard for fire sprinkler systems fed from the domestic water system. It is an adaptation of AS 2118.5 to facilitate the use of cost-effective sprinkler systems in mid-rise buildings.
The system takes its water supply from the building’s domestic water riser, downstream of the domestic pump. This eliminates the need for a dedicated sprinkler system water supply tapping, pump set, control valve assembly and riser.
The FPPA101H Standard is a design standard for sprinkler systems fed from the hydrant system. The system consists of a typical internal hydrant installation commonly required for a Class 2 or Class 3 buildings where coverage cannot be achieved by external hydrants and includes a feed for the sprinkler system which is taken at each floor level directly from the hydrant riser.
In comparison to an AS 2118.1 or AS 2118.4 system, this standard eliminates the need for a dedicated sprinkler system water supply tapping, pump set (if necessary), sprinkler control valve set and sprinkler riser.
Rather than having its own dedicated sprinkler water supply into the building this sprinkler system is integrated with the domestic water supply to the building.
Each floor will have a branch from the domestic riser to feed the sprinkler system and domestic water for that floor. The branch will include an isolation valve to isolate the domestic water from the sprinkler stem on the floor. A further branch to serve the sprinkler system will be taken into the sole-occupancy unit (SOU) and connected to the toilets in each SOU.
This branch will incorporate a back flow prevention device after the take off point and then reticulates throughout the corridors and common area and into each sole occupancy unit.
How do you know if the system is still functioning?
Any interruption or reduction in the water supply to the shower, taps, etc. will alert the occupants to an interruption to the water supply to the sprinkler system.
If the cistern to the toilet fails to fill or has a reduction in filling, the occupants will be alerted that there is an issue with the water supply to the sprinkler system.
What buildings does this system apply to?
This system only applies to the Class 2 or Class 3 parts of a building not more than 25m in effective height. If the building contains other classes or parts of a building they will be required to use an AS 2118.1 sprinkler system if:
Rather than having its own dedicated sprinkler water supply into the building this sprinkler system is integrated with the hydrant system water supply to the building. The system takes its water supply feed at each floor level directly from the hydrant riser. Once the feed is taken at each floor level a typical sprinkler piping layout is then provided to each residential floor.
There are some specific limitations on the use of the FPAA sprinkler standards.
These systems can be used in Class 2 or Class 3 parts of a building not more than 25m in effective height which can incorporate Class 5 ,6, 7, 8 or 9b building provided a sprinkler system to those other classes of buildings are in accordance with Specification E1.5a and the relevant provisions of Specification C1.5.
It is important to check with your local authority or administration for any specific state or territory provisions that can override the NCC provisions.
You should also check with your local authority or administration regarding transitional arrangements and what version of the NCC applies to your project.
You can download the new editions of the NCC from the ABCB website or order a hard copy from HIA.
The ABCB and the FPA Australia have also developed a range of resources to assist in understanding and applying the new sprinkler changes.