Two of the most common questions HIA receives on waterproofing are ‘when do you need to install a floor waste?’ and ‘does it require fall in the floor to the waste?’ There is much anecdotal evidence out there in relation to this, but what are the facts?
There are two primary documents in relation to wet areas construction:
Both contain information on materials and methods required in relation to waterproofing bathrooms and wet areas such as WCs and laundries.
The NCC has two parts: Volume 1 for Class 2 - 9 buildings and Volume 2 ‘Housing Provisions’ for Class 1 and 10 buildings.
NCC Volume 2 references or ‘calls up’ AS 3740 as an NCC primary referenced document. AS 3740 contains the detailed waterproofing of wet area provisions for Class 1 buildings (houses). NCC Volume 1 also applies AS 3740 to certain classes of commercial buildings.
There are several things to consider in determining if a floor waste needs to be installed.
You also need to consider the requirements and options available for sanitary drainage under the Plumbing Code of Australia (PCA) and AS/NZS 3500.2.
For apartment buildings (Class 2 buildings), hotels, motels and boarding houses (Class 3 buildings), and residential parts of commercial buildings (Class 4 parts of a buildings), NCC Volume One requires a floor waste be installed in bathrooms and laundries if a bathroom or laundry is situated at any level above a sole-occupancy unit or a public space. A public space in a building would include areas such as public foyers and reception areas.
In these circumstances the floor to the room is required to be waterproof and the floor graded to the floor waste to permit drainage of the water. The required fall of the floor, the waterproofing requirements of the floor and the installation details of the floor waste are specified in the NCC.
The intent of this provision is to provide protection from flooding to an adjoining separate unit or a public area.
NCC Volume One Also requires installation of a floor waste in any room containing a urinal in a Class 2-9 building.
Class 1 buildings ‘require’ a floor waste be provided within the shower area. This is indicated in both the NCC and AS 3740.
The NCC defines a shower area as the area affected by water from a shower, including a shower over a bath and for a shower area that is -
The required fall of the floor, the waterproofing requirements of the floor and the installation of the floor waste are specified in the NCC.
For the area outside of the shower area an additional floor waste is not ‘required’ to be provided, nor is one ‘required’ to be provided in other wet areas such as in a laundry or in a WC. For an unenclosed shower, the floor outside the shower can be graded to the shower waste.
For a shower over a bath that is ‘unenclosed’ the NCC and AS 3740 ‘requires’ an additional floor waste be provided (see Figure 1). In this case, 'unenclosed' means the shower over bath is not provided with a minimum 900 mm wide screen for the open side of the bath that contains the water within the bath.
It should be noted that these requirements are the minimum requirements only. A designer or builder may choose to install an additional floor waste (i.e. in addition to the one in the shower area) or provide one to the floor in a laundry or WC voluntarily. In this case the floor must fall to the waste.
Plumbing & drainage requirements for all classes of buildings are set out in Plumbing Code of Australia (PCA). In turn the PCA references the AS/NZS 3500 suite of standards for the detailed technical requirements for plumbing & drainage installations.
Specifically, AS/NZS 3500.2 sets out the sanitary plumbing and drainage requirements and these requirements are replicated in AS 3500.5 (Housing Installations).
AS/NZS 3500.2 contains several provisions relating to the installation of floor waste gullies in bathrooms as part of the installation of certain waste fixtures such as baths, basins, showers, laundry tubs etc.
However, it should be noted that AS/NZS 3500.2 does not prescribe that a floor waste gully must be installed, rather it is listed as an option as part of the installation of the waste fixture(s). For example a bidet can be installed with a trap and waste pipe or with an untrapped waste pipe to a floor waste gully.
An individual shower must be fitted with a DN80 (minimum) grate or channel grate that discharges via:
Clause 13.3.6 of AS/NZS 3500.2 states if a fixture trap is not accessible the grate shall be removable. This applies to the shower trap.
For bath installations, AS/NZS 3500.2 contains a few options:
Where a floor waste gully is used:
Drainage via an accessible trap:
It is relatively simple to achieve an accessible trap in a house with a suspended floor, or in an upstairs bathroom. This can be via a snap vent or other access panel.
In a slab-on-ground, designing an accessible trap under a bath is more difficult. An accessible trap may still be possible via:
HIA is aware that there are some differing views as to whether a floor is required to be graded to the floor waste:
NCC 2022 has been amended to more explicitly require that a floor be graded to the floor waste and meet other compliance requirements where a floor waste is installed. The requirement to provide a continuous fall in the plane of the floor is prescribed in the NCC. ABCB Housing Provision Standard Clause 10.2.12 and F2D4 of NCC Volume One.
The NCC now specifies that where a floor waste is installed, be it to meet a mandatory requirement of NCC or installed voluntarily, that the floor must fall to that floor waste meeting prescribed grades that being a maximum fall of 1:50 and minimum fall 1:80.
If you wish to use an alternative arrangement to either achieve the drainage requirements of the PCA or the fall in the floor under the BCA, it is possible to develop a Performance Solution. These will need to go through approval process required in your jurisdiction.
F2V1 of NCC Volume One also allows the BCA's overflow requirements to be achieved by verification that the capacity of installed overflow devices exceeds the flow rate of the source, under a simple Performance Solution for bathrooms, laundries and the like Class 2,3 or 4 parts.
As some states maintain variations to the NCC which alter options for compliance in some circumstances, it is also important to check with your local authority or administration for any specific State or Territory provisions in relation to the installation of floor wastes that may override the NCC or Australian Standards provisions.
HIA have a guide to wet area waterproofing that explains your obligations,practical examples for compliance and more. You can purchase the guide below.
Can’t find what you need, check out other resources that might be closer to the mark.
Silica exposure training will be mandatory for all building and construction workers in ACT from 1 July 2023. This course provides the skills and knowledge to work with silica dust and to implement safe work systems to prevent exposure.
Gain an understanding in relation to the substantial changes to the energy efficiency provisions contained within NCC 2022.
Learn about the important updates and changes included in the NCC 2022 for internal and external waterproofing.
Gain a basic awareness of asbestos - where it may be found; its health hazards; and the safety control measures that should be applied to prevent exposure of workers and others.
Enter your email and password to access secured content, members only resources and discount prices.
Did you become a member online? If not, you will need to activate your account to login.
If you are having problems logging in, please call HIA helpdesk on 1300 650 620 during business hours.
If you are having problems logging in, please call HIA helpdesk on 1300 650 620 during business hours.
Enables quick and easy registration for future events or learning and grants access to expert advice and valuable resources.
Enter your details below and create a login